Numerical study on the cooling performance of dry cooling tower with vertical two-pass column radiators under crosswind
Abstract
To study the cooling performance of a natural draft dry cooling tower with vertical two-pass column radiators (NDDCTV) under crosswind, a three-dimensional (3D) numerical model was established for NDDCTV and validated by some published results. By the numerical model, the aerodynamic field around cooling columns was computed and analyzed at 4 m/s crosswind. It was found that the large inflow air deviation angle at delta entry induced large eddy...
Paper Details
Title
Numerical study on the cooling performance of dry cooling tower with vertical two-pass column radiators under crosswind
Published Date
Jan 1, 2015
Journal
Volume
75
Pages
1106 - 1117
Citation AnalysisPro
You’ll need to upgrade your plan to Pro
Looking to understand the true influence of a researcher’s work across journals & affiliations?
- Scinapse’s Top 10 Citation Journals & Affiliations graph reveals the quality and authenticity of citations received by a paper.
- Discover whether citations have been inflated due to self-citations, or if citations include institutional bias.
Notes
History